Date: August 1, 2025
Zip Code: 32204
City: Jacksonville
Electrician Notes
-Found loose breakers in Panel C, that seemed to cause heat damage to (3) 2-pole 60A GE Bolton breakers.
-Safed off.
-Ordered replacement breakers.
8/4/25
-Installed rodent guards on TX-DA, rodent guards would not fit TX-CA. (no charge).
-Replaced outlet MDP-14-1618, Loose wire on breaker in workshop.
-Replaced (3) 2-pole 60A breakers in panel C.
-Checked all terminations and breakers all tight.