Jacksonville Electrician Logs
W72930
Date: April 10, 2025
Zip Code: 32259
City: St. Johns
Electrician Notes
Old septic pump and alarm outlet not GFCI protected. Two circuits at septic, one for alarm and one for septic pump. Old outlet in single gang nail on bolted to PVC box without cover/missing cover. Removed PVC box, cut off 3/4in MH and installed 3/4in FA, extended with carflex, installed 2-gang bell box with two GFCI’s and 2-gang bubble cover. Mounted septic alarm, landscaping GFCI, and chicken coop GFCI not working. Traced landscaping/coop GFCI to bell box at right side of house and fed from pool control box. Disconnected at pool control box. Pulled THHN from existing bell box to pool panel. Used existing 20A breaker (breaker was spare/unused). Replaced GFCI and cover at landscaping. Landscaping feed chicken coop. Put old cover on dock PVC box. PVC box at dock needs to be replaced. Replaced bell box blanks on two boxes at right side.